IS3 Export

hacs Validate

English · Česky

UNOFFICIAL Home Assistant integration for iNELS central units (ELKO EP). It talks to the unit directly over UDP port 9999 — the same port the unit's own configuration software connects to — so it needs no Connection Server. The "IS3" in the name is iNELS3, the .is3 export format it is based on.

Nothing has to be enabled on the unit. Every unit tested answered on that port as it came and pushed changes on its own — no port to open, nothing to switch on in IDM3.

The device list comes from the unit's .is3 export: downloaded straight from units that serve it over HTTP, or saved out of IDM3 and dropped into the setup form for those that don't — the newer units serve no export over HTTP (confirmed on a CU3-08M), so there you upload it once.

Status: experimental. Read What has been tested before assuming your unit is covered — part of the range is verified on live hardware, part only expected to behave the same. Covers report an assumed state, no position feedback; see Limitations.

How the protocols were established, and what this software is and isn't: NOTICE.md.

What has been tested

Control — reads, writes, events, heating, dimmers, buttons — is verified on the reference installation, a classic CU3-0x on IDM3 03-04-19, and reads and writes on a CU3-08M on IDM3 03-05-03. That second one is the point of this release: the new generation could not be reached at all before it.

What the table below is about is the one thing that still differs — whether the device list can be imported automatically, or has to be saved from IDM3 and uploaded once.

Unit IDM3 Automatic import
CU3-01M, CU3-02M (identical to each other) 03-03-34, 03-04-19 ✅ tested, works
CU3-08M 03-05-03 ❌ tested, does not — upload the export
CU3-07M, CU3-09M, CU3-10M expected to behave like the 08M; not tested

The export parser has a wider base: exports from several installations, 17 to 1125 items, written by IDM3 03-03-34 through 03-05-03. If you run a unit that isn't in this table, saying what happened — either way — is how it grows.

Firmware updates can change this

What the integration speaks was recovered by observation, not from a specification, so a firmware update can change it with no warning.

  • Verified against units running IDM3 03-04-19 and 03-05-03. Other versions are untested — which is not the same as known-broken.
  • If an update breaks the wire format, the client warns once, loudly in the log and names what it got instead.
  • Run compat_check.py before an update and keep the file — it fingerprints every assumption the integration makes and afterwards says which of them moved and what that costs you. Read-only, and it prints nothing that identifies the installation, so the output is safe to paste into an issue.
python tools/compat_check.py 192.168.1.10 --save before.json
# ... update the unit's firmware ...
python tools/compat_check.py 192.168.1.10 --compare before.json

How state stays in sync

The unit pushes every change it makes — a relay flipped from the wall, a new temperature reading, a button press — with nothing ticked anywhere to ask for it. Commands from Home Assistant are verified by reading back: if the output didn't take, or a wall switch flipped it in the meantime, the state corrects itself instead of leaving the icon stuck. The unit acknowledges a write in 4 ms, and its own push event for that write arrives 0.13 s later.

On top of the events, every readable address is re-read on a 30-second cycle — reading the whole installation (313 readable addresses) takes 0.13 s — so an address whose events stop arriving is back in step within one cycle. Buttons are left out of that re-read, or it would replay a press nobody made.

The device list follows too: each cycle the unit is asked for a digest of the project loaded in it, and the export is re-fetched only when that digest changes — that is, when the installer republishes from IDM3.

Installation

It's in the HACS default store: open HACS, search IS3 Export, Download it, restart Home Assistant, then add the integration. The two buttons do the same in one click each:

Add repository to HACS Add integration

Manually: copy custom_components/is3_export into config/custom_components/.

Configuration

Field Description Default
Host The unit's IP address
Port UDP. Change it only if the unit is reached through a tunnel or a forwarded port. 9999
Central unit password the password set on the unit in IDM3; leave empty if none is set, which is the usual case empty
Export file path leave empty, it downloads from the unit empty
Export file upload for units that serve no HTTP export — drop the .is3 saved from IDM3 here; it is kept under config/is3_export/

The integration's name comes from the export header. The password is for the unit, not for the export — the unit serves the export as a static file with no login; if one blocks the download anyway, upload the export or give the path to a locally downloaded one.

Correct any of it later under Settings → Devices & services → IS3 Export → ⋮ → Reconfigure. The same menu → Delete removes every entity and device it created; nothing is left behind on the unit, and no files outside custom_components/is3_export.

Upgrading from 0.1.x

0.2.0 replaces the transport: everything now goes over UDP port 9999. Existing installations upgrade in place, keeping entity ids, areas and history.

  • The port is rewritten to 9999, whatever was stored before.
  • Two connection settings the old transport needed are gone, along with the repair issue that complained about them.
  • If the unit has a password set in IDM3, Home Assistant raises its usual re-authentication dialog. If none is set, nothing is asked.
  • Worth doing by hand: untick Third part setting in IDM3. That setting lives in the unit, so nothing here can turn it off for you — and while it is on, the unit keeps a door open that takes no password and that this integration no longer uses.

0.2.1 moves fans. An output named Vent_… used to be a switch that looked like a fan; it is a fan entity now, so switch.…_vent_x becomes fan.…_vent_x. Automations and dashboards pointing at the old one need the new name.

Rolling back to 0.1.x means deleting the integration and adding it again — entity ids, areas and history go with it, so take a backup first if you want that door left open.

Which addresses become entities

The second byte of the address determines the type:

Address Meaning Entity Write
0x0102 relay switch
0x0104 dimmer (with % unit) light 0–100 %
0x0203 SYSTEMBIT switch
0x0202 SYSTEMINTEGER number
address pair blind cover
controller channels heating zone climate
0x0101 inputs, buttons, controller status outputs binary_sensor
0x0107 module faults binary_sensor (problem)
0x0105 temperature / humidity sensor
0x0108 analog input (a Light-IN input reads illuminance / lux) sensor
0x0103, 0x0111, 0x0112 controller channels sensor
0x0206 water meters, electricity meters sensor (total)
0x0501, 0x0204, 0x0209, 0x0003 plans, groups, schedules

Writes happen only where a write is documented — never to inputs, thermostat channels, or plans. The hardware ID decides, not the name: anything starting with Controller_, Heat-Regulator_ or Cool-Regulator_ is controller internals and is not written to, while an unnamed relay (_ SA3-04M_RE2_…) is still a relay.

Names refine the entity type

The address says what the output is; the name says what it's for.

In the name Entity Icon
imp button
sv light light bulb
lamp light floor lamp
zrc light mirror
LED light LED strip
vent fan
zas switch socket
TL (or DIN input) event (press + long_press)

Names split on _ and -, case doesn't matter, and the more specific rule wins (imp_sv_chodba is a button). sv, imp, vent, zas and TL must match as a whole token (otherwise Svod_vody would be a light and Zastineni a socket); lamp, zrc and LED are enough as a prefix. An imp button sends a pulse on press, so the next press is again a fresh edge for the iNELS program.

TL_ makes an event button on any module. A DIN input is a button on wall controllers and on the central unit itself (In-Out); on other modules (e.g. the IM3 input module) it stays a plain binary_sensor — a maintained contact — until you name it TL_. Wired buttons distinguish press from long_press (see Wall switches).

The light and switch tokens apply only to relays and dimmers and never make anything writable (an input named Sv_okno stays a binary_sensor); TL/DIN apply only to digital inputs. There are deliberately no more rules — override the entity type or icon in Home Assistant if something comes out differently.

Blinds

Several addresses combine into one cover entity, from three possible sources:

  1. System bits of the blind program (0x0203) — up, down, stop, tilt. The program in the unit drives the contacts and stops the blind itself. Preferred where present.
  2. A pair of JA3 relays — direction is in the hardware ID (JA3-018M_Up1 / Down1); stop by releasing both.
  3. A plain relay pair (an SA3 module, including the SA3-02B box) — two relays on one motor, interlocked in hardware. Here the direction is in the name: an UP/DOWN token anywhere in it (Roleta_loznice_UP, …_UP_…) pairs the two halves that share the same module.

A bare relay won't release itself, so a relay blind (forms 2 and 3) gets a travel-time number entity (default 30 s): the relay is released once that time elapses, so set it to the blind's real run time, a touch more, and it reaches the end stop first. Reversing releases the opposite direction first, waits briefly, then drives.

Two outputs that each belong to a different heating zone are deliberately left as two switches — a wrong pairing there would drive real relays. No form reports its position, so a cover carries an assumed state, and addresses taken by a blind no longer appear as switches.

Heating zones

A heating controller is a set of channels with the same serial suffix plus a named root <name> Controller_<serial>. Together they form one climate entity:

Channel
current temperature Actual-Therm-AOUT
target temperature Required-Therm-AOUT (heating) / Required-Cool-Therm-AOUT (cooling)
heats / cools Required-Heat-DOUT / Required-Cool-DOUT
preset Control-Manual-IN — 0 Schedule, 1–4 Preset 1–4, 7 Manual
heating / cooling Control-HC-IN — 0 heating, 1 cooling
on / off Control-IN — 0 off, 1 on

Cool is offered only for a zone that actually has a cooling output wired — every zone carries the cooling channels, so their presence alone means nothing. Setting the temperature switches the zone into Manual; preset values 1–4 and the weekly plan behind Schedule are set on the unit, not here.

Each zone also has a select plan — Normal / Vacation / Holiday. Holiday is a daily program and must be configured on the unit; where it isn't, the switch doesn't take and the read-back squares the plan back in the UI.

Wall switches (WSB3)

A single switch breaks down into one entity per channel:

Type Breakdown into entities
WSB3-20 8 — 2 buttons (up/down) + 2 LEDs (green/red) + 2 temperatures + 2 digital inputs
WSB3-40 12 — 4 buttons + 4 LEDs + 2 temperatures + 2 digital inputs
WSB3-*-Hum +2 — humidity (%, device_class humidity) and dew point (°C)

The indicator LEDs (roles Green/Red) are switches with a G/R icon, taken from the role, so even unnamed ones get it.

Buttons (Up/Down/DIN) are event entities. Wired ones distinguish a short press from a long_press — a hold counts as long after 1.5 s, the same threshold as in iNELS, and the event fires at that moment rather than on release. That covers the whole wired wall-controller family: GSB3, GSP3, MSB3, GBP3, GRT3, the card readers GMR3/GCR3/GHR3/GCH3, the info panels GDB3, WMR3, the room controller IDRT3. Short/long rests on events arriving when they happen, so anything that delays them smears the hold duration — see Other things talking to the unit.

RF controllers report press only, and a held RF button fires it more than once — see RF devices. IBWL (RF input module) is the exception: each input mirrors a paired RF device — a button, but also a door or motion sensor, indistinguishable in the export — so it stays a binary_sensor until you name it TL_. Proximity sensors and card readers are not buttons.

Devices, and what is hidden

Every physical module (by the serial number in the hardware ID) is its own device in HA, nested under the central unit, so the channels of one switch or relay board stay together. System things (bits, integers, buttons) have no module and sit directly on the central unit.

Large installations export hundreds of panel internals — button contacts, indicator LEDs, fault flags. Entities are created from them but are disabled by default; enable them in the integration settings. Unnamed ones get their name from the role in the hardware ID (e.g. Up, Green). Also disabled, even when named: the SW status inputs of relays and the fault/alert flags (OUF-Alert, 0x0107, device_class problem, diagnostic).

A wall panel's indicator LEDs (Green1, Red2) are treated differently again: enabled but hidden. They stay switchable from an automation, they are simply kept out of the generated dashboards — a house of wall panels has more backlights than lamps, and they would crowd out the lights you meant to see. Unhide one under its entity settings. This applies to entities created from 0.2.1 onwards; on an installation set up before that, Home Assistant keeps the visibility it already recorded.

RF devices

A device on an RF module (e.g. an RFKEY remote) is its own device. Its buttons are event entities firing press only; Battery_LOW is a binary_sensor with device_class battery.

An RF button held down fires press more than once. The module re-sends "down" about every 1.5 s while the button is held, and each of those is a press as far as anything here can tell — a two-second hold measured on a live RFKEY produced two. A wired button does not do this. If an automation on an RF button must not run twice, give it a cooldown (mode: single with max_exceeded: silent, or a condition on the last trigger).

What's in the export, and values

The export is not a list of everything — in IDM3 you choose what goes into it. If something's missing in Home Assistant, add it there and republish: the integration notices on the next cycle and reloads itself (see How state stays in sync); Reload does it at once.

Temperatures and humidities come in multiplied by a hundred — 2550 means 25.50 °C. Dimmers are already in percent. SYSTEMINTEGER is a raw value; what it means is up to the program that uses it. Counters (0x0206) report the unit's real totals.

Utility meters

A meter's pulse must be counted in the central unit, not in Home Assistant. Add a counter over the pulse input in IDM3; it then comes through here as a sensor (a 0x0206 total), and if you give it a kWh, or similar unit it is tagged energy / water / gas, ready for the Energy dashboard.

Do not count the pulses in Home Assistant. A meter's pulse is a brief, frequent contact and arrives as a binary_sensor input (e.g. Pulz_meter); Home Assistant reads state on a cycle and cannot see each short edge, so a counter built over the input undercounts badly. The unit counts in firmware and never misses one — which is why the integration exposes the raw input but leaves the counting to the unit.

Everything above the counter is per-installation and belongs in Home Assistant, not here: dividing the count by the meter's imp/kWh (a template sensor), the two-tariff split (a utility_meter switched by your HDO signal), and the Energy dashboard. Setups vary — two pulse outputs for the two tariffs, or one pulse plus an HDO contact for low tariff — so there is no single rule to build in.

⚠️ Security

The unit's authorization is not a real barrier. It accepts an empty password by default, which is how most units are left — so anyone who reaches the unit on the network can control the entire installation. Setting a password in IDM3 raises the bar; nothing is encrypted either way. Keep the unit on a separate VLAN, or at least firewall it off from untrusted devices and from the internet.

Limitations

  • Covers report no position. A cover shows an assumed state (open / closed / moving), not a percentage; a relay blind's end stop is inferred from the configured travel time, not measured.
  • Scenes can't be triggered — a read on them returns no value, and writing is unverified.
  • The binary .otc / .cld formats are not read. They additionally contain named scenes.
  • Nothing is encrypted — neither the HTTP export nor the port 9999 traffic.

Other things talking to the unit

Measured: the unit's configuration software connected at the same time costs almost nothing — a single read still took a median of 4 ms and the whole installation 179 ms (against 130 ms with it gone), writes were acknowledged in 8 ms, and the event stream ran throughout. Leave Home Assistant running while you work on the project.

Not measured: how this behaves alongside a running iNELS Connection Server. Expected to be fine, but nobody has checked — if you run one, please open an issue with what you see.

Diagnostics

  • Unit status sensor (diagnostic) on the central unit: running, running fast or stopped. A stopped unit still answers and holds its last values, so without this everything looks normal in Home Assistant while nothing in the building responds. Its unit_clock attribute is the unit's own clock — heating schedules run off it, so an hour's disagreement (a unit left on winter time) switches your heating at the wrong hour.
  • Download diagnostics from the integration's menu: a redacted snapshot of the config, the unit's capabilities, and every entry with its live value and how it was classified. Host and credentials are masked, so it's the quickest thing to attach to a bug report.
  • tools/probe_is3.py <ip> answers the same questions from outside Home Assistant when the integration won't set up at all — whether the unit responds, wants a password, opens its data plane, and pushes events. Prints addresses and values, never device names; read-only unless you pass --write.
  • tools/compat_check.py before a firmware update — see Firmware updates can change this.

Development

pip install -r requirements-test.txt
pytest

On Windows read CONTRIBUTING.md first — it saves an afternoon (Python 3.13, a short venv path, and an lru-dict wheel trick).

The other way into a unit is XML-RPC on the iNELS Connection Server (port 7801), which this integration doesn't use; for that route there's InelsForHass.